140NOA62200C Interbus Master Module for Modicon Quantum

Product Introduction

The 140NOA62200C Interbus master module expands the communication capabilities of Schneider Electric Modicon Quantum automation platforms. This unit serves as a master device on the Interbus network, enabling seamless data exchange between the Quantum CPU and remote I/O stations. Specifically designed for severe environments, this module ensures reliable operation even in demanding industrial conditions.

Technical Specifications

The 140NOA62200C operates using twisted pair cabling with a maximum cable distance of 20 meters between devices. The communication protocol runs on Interbus RS485 at 500 kbit/s, conforming to DIN 66020 standards. This module uses the master method of access, giving it control over bus communication and data exchange with connected slave devices.

For power requirements, the 140NOA62200C draws 800 mA from the Quantum backplane. Power dissipation measures 4 W, ensuring efficient thermal performance within the rack. The module occupies a standard format slot and installs in a local rack configuration.

Memory Architecture and Firmware

This Interbus master module incorporates a sophisticated memory structure to handle complex communication tasks. It includes 128 kB + 256 kB firmware EPROM2 kB dual-port RAM, and 256 kB + 32 kB for data RAM. Additionally, it features 64 kB Interbus command sequence EEPROM and 64 kB multi-port RAM. This ample memory capacity supports extensive I/O mapping and efficient data handling.

Software Compatibility

The 140NOA62200C works seamlessly with Schneider Electric programming software. Specifically, it supports Concept and ProWORX 32 software versions V 2.5 SR2. The module is compatible with various Quantum CPUs including 140CPU53414B140CPU43412A, and 140CPU11303. For local rack configurations, it supports up to 6 x 140CPU11303 units or 2 x 140CPU43412A/140CPU53414B units.

Communication Performance

The module profile supports PCP V2.0, enabling parameterization and data exchange with intelligent field devices. The Interbus generation 4 architecture ensures high-speed, deterministic communication for critical automation tasks. Furthermore, the isolated RS485 interface provides protection against electrical interference, enhancing signal integrity in noisy industrial environments.

LED Indicators and Diagnostics

The 140NOA62200C features an extensive array of LED indicators for comprehensive status monitoring:

  • ACTIVE (green): Communication with Quantum CPU is active

  • RUN (green): Firmware and module are running normally

  • IS-B RUN (green): Interbus is functioning and carrying data

  • F (red): Module fault detected

  • DEA 202 fault (red): Initialization fault

  • Interbus not operational (red): Master communication failure

  • Interbus fault (red): Module has reported a bus fault

  • Memory fault (red): Memory error detected

  • Peripheral bus fault (red): Peripheral communication issue

  • Processor fault (red): Master processor failure

  • Remote bus fault (red): Remote bus segment issue

  • Bus segment shutdown (yellow): One or more bus segments are disabled

This comprehensive diagnostic suite enables rapid troubleshooting and minimizes system downtime.

Environmental and Physical Specifications

The 140NOA62200C operates reliably within an ambient temperature range of 0°C to 60°C. For storage, it withstands temperatures from -40°C to 85°C. Humidity tolerance reaches 95% without condensation, ensuring performance in humid environments. Operating altitude extends to 5,000 meters, providing deployment flexibility.

For electrical protection, the module resists electrostatic discharge of 4 kV contact and 8 kV on air, conforming to IEC 801-2. Electromagnetic field resistance meets 10 V/m at 80-1000 MHz per IEC 801-3.

Installation and Setup Guidance

Installing the 140NOA62200C requires following a systematic procedure. First, disconnect all power sources to the Quantum rack. Next, align the module's connectors with the corresponding slot on the backplane. Then, slide the unit firmly into place until it locks securely.

For network wiring, use twisted pair cable and connect to the SUB-D 9 connectors on the front face—one for the Interbus link and one for additional connections. Configure the module using Concept or ProWORX 32 software, setting the appropriate parameters for your Interbus network. After powering up, observe the LED indicators to verify normal operation.

Applications and System Integration

The 140NOA62200C fits seamlessly into industrial automation applications requiring distributed I/O connectivity. Specifically, it excels in material handling systems, packaging lines, and assembly machines where Interbus networks are prevalent. Its severe-environment design makes it suitable for facilities with vibration, dust, or temperature variations.

Packaging and Delivery Information

Each 140NOA62200C module ships in a sealed anti-static bag to prevent electrostatic discharge damage. The bag then rests inside a sturdy cardboard box with adequate cushioning material. Inside the package, you will find the Interbus master module itself. This packaging arrangement guarantees safe transit to your facility.

Shipping and Logistics

We dispatch all orders using premium international couriers including FedExUPS, and DHL. These services ensure prompt delivery with full tracking capabilities. Once we ship your order, we will provide a tracking number for your reference. Consequently, you can monitor your shipment's progress from dispatch to final delivery.

Frequently Asked Questions

1. What is the maximum cable distance for the 140NOA62200C?
This module supports a maximum cable distance of 20 meters using twisted pair cabling.

2. Which CPUs are compatible with the 140NOA62200C?
It is compatible with 140CPU53414B140CPU43412A, and 140CPU11303 Quantum CPUs.

3. What bus current does the 140NOA62200C require?
The module requires 800 mA from the Quantum backplane.

4. How many LEDs does the 140NOA62200C have for diagnostics?
It features 12 LED indicators for comprehensive status monitoring and fault diagnosis.

5. What certifications does the 140NOA62200C hold?
It holds UL and CSA certifications, confirming compliance with industrial safety standards.



Attention: The above product information is sourced from the internet and cannot be guaranteed to be authentic. For specific product parameters and prices, please contact SpareTech PLC professionals in a timely manner.
Brand Name
Model No.140NOA62200C
Product TypeInterbus Master Module
hasMerchantReturnPolicyAdjust according to reality
ShippingdetailsAdjust according to reality
The 140NOA62200C is an Interbus master module from Schneider Electric for Modicon Quantum systems. Designed for severe environments, it uses twisted pair cabling and delivers reliable communication for industrial automation networks.
SpareTech PLC provides you with a PDF version of the instructions about N/A 140NOA62200C, where you can download the N/A 140NOA62200C manual PDF for free:
Download PDF

Get a Professional Quote