Manufacturer: N/A Series: N/A Model Number: 900SP1-0100 Weight: 0.85kg Condition: In Stock Availability: 100% Original Brand New Product Origin: U.S.A Shipping port: Xiamen Warranty: 12 Month
Honeywell 900SP1-0100 I/O Interface Module
Product Introduction
The Honeywell 900SP1-0100 serves as the interface module between expansion I/O and the control processor module. This unit is required when I/O racks must communicate with CPMs located in a different rack. Specifically, it bridges remote racks and the main controller over a dedicated I/O network.
Furthermore, the module runs on a dual-core ARM Cortex-A9 processor clocked at 667 MHz. A rotary address switch sets the rack address range from 1 to 99. Two tri-color LEDs report the module status at a glance. Besides, dual shielded RJ45 ports with auto-crossover and auto-detecting 10/100BaseTx speed simplify cabling in both redundant and non-redundant systems.
Technical Specifications
Processor and Indicators
Item
Specification
Processor
Dual Core ARM Cortex-A9 (32 bit), 667 MHz
Rotary Address Switch
Rack address range 1 to 99
LED
2 LEDs, three color each, EPM status
Communication Capabilities
Item
Specification
Ethernet Ports
2
Network Connector
Shielded RJ45, auto-crossover
Port Speed
10/100BaseTx, auto-detecting
Isolation
1500 Volts RMS, 1 minute, 60 Hz
Transient Voltage Suppression
600W peak pulse power at 10×1000μs waveform, 0.01% repetition rate
Diagnostic LEDs
Yes, on each port
Protocols (Ports 1 & 2)
I/O Communication
I/O Network Topology
The ControlEdge 900 platform supports both Star and Ring topology to connect expansion I/O racks with the CPM rack.
Item
Specification
Topology
Star or Ring, up to 100BaseTx, standard RJ45, redundant and non-redundant systems
Max Cable Length (Copper)
100 m (328 ft.) CPM to EPM or to switch, shielded Ethernet cable
Max Cable Length (Fiber)
5000 m (16404 ft.) CPM to EPM or to switch
Mechanical and Environmental Parameters
Power and Thermal
Item
Specification
Power Consumption
2.6 W
Heat Dissipation
2.6 W
Operating Environment
ControlEdge 900 rack environment
Isolation Rating
1500 Volts RMS for 1 minute at 60 Hz
Recommended Network Equipment
Qualified fiber optic equipment keeps long-distance links stable. For instance, the Moxa EDS-308 unmanaged switch offers eight 10/100 ports and needs 24VDC power. Meanwhile, the EDS-308-MM-SC adds two multi-mode fiber ports with SC connectors. Besides, the EDS-316-MM-SC provides fourteen copper ports plus two fiber ports. The Moxa IMC-101-M-SC converter changes 10/100BaseT(X) to 100BaseFX multi-mode fiber. Use shielded CAT5 cable for copper runs and multi-mode duplex 62.5/125 fiber with SC connectors for fiber runs.
Installation Guide
First, set the rotary address switch to a rack address between 1 and 99. Next, mount the 900SP1-0100 in the expansion I/O rack and confirm secure seating. After that, connect port 1 and port 2 with shielded RJ45 plugs or qualified fiber converters. The auto-crossover feature removes the need for special crossover cables.
Moreover, verify the link and diagnostic LEDs on each port after power-up. The tri-color status LEDs should show a healthy state before you enable I/O communication. Finally, confirm the Star or Ring topology matches your network plan, and keep copper runs within 100 m while fiber runs may reach 5000 m. Therefore, plan cable routes and switch placement before commissioning.
Q1: What is the main function of the 900SP1-0100? A1: It acts as the interface between expansion I/O racks and control processor modules in a different rack. Hence, remote I/O racks can communicate with the CPM over the I/O network.
Q2: Which network topologies does this EPM support? A2: The module supports both Star and Ring topology at up to 100BaseTx. Additionally, it works in redundant and non-redundant systems with standard RJ45 connections.
Q3: What is the maximum cable length for the I/O network? A3: Shielded copper cable reaches 100 m (328 ft.) from CPM to EPM or switch. Fiber optic cable extends to 5000 m (16404 ft.) with qualified Moxa converters and switches.
Q4: How is the rack address configured? A4: A rotary address switch on the module sets the rack address range from 1 to 99. Specifically, you select the address before power-up and commissioning.
Q5: What are the power consumption and shipping options? A5: The module consumes 2.6 W and dissipates 2.6 W of heat. We ship orders by Fedex, UPS, and DHL with tracking support.
Attention: The above product information is sourced from the internet and cannot be guaranteed to be authentic.
For specific product parameters and prices, please contact
SpareTech PLC professionals in a timely manner.
Brand Name
Model No.
900SP1-0100
Product Type
Expansion Processor Module
hasMerchantReturnPolicy
Adjust according to reality
Shippingdetails
Adjust according to reality
The Honeywell 900SP1-0100 is an Expansion Processor Module for the ControlEdge 900 platform. It links expansion I/O racks to control processor modules, enabling reliable Ethernet-based I/O communication. SpareTech PLC provides you with a PDF version of the instructions about
N/A 900SP1-0100,
where you can download the
N/A 900SP1-0100 manual PDF for free: Download PDF