Yokogawa UT32A-000-11-00 Digital Indicating Controller

Product Introduction

The Yokogawa UT32A-000-11-00 belongs to the UTAdvanced series. This digital indicating controller packs many features into a compact 1/8 DIN housing. Its 14-segment active color LCD shows process values clearly. The display changes color to alert operators.

Navigation is simple with five keys: SET/ENTER and four arrow keys. Therefore, you spend less time learning and more time controlling. The UT32A also includes a ladder sequence function as standard. This allows basic logic control without extra hardware.

Multiple communication options are available. However, this base model supports CC-Link and RS485. For Ethernet, choose a different suffix. The controller meets IP66 and NEMA4 ratings for the front panel. As a result, it handles washdown environments well.

Key Technical Specifications

The Yokogawa UT32A-000-11-00 delivers reliable performance. Below are the critical details.

Display

  • PV display: 5-digit, 14-segment active color LCD (white/red)

  • Character height: 13.0 mm

  • Data display: 5-digit, 11-segment color LCD (orange)

  • Bar graph: 12-segment color LCD (orange)

Universal Input

  • Number of inputs: 1 point

  • Supports thermocouple, RTD, voltage, and current

  • Accuracy: meets Yokogawa standards for each sensor type

Control Output

  • Heating output: 1 point (shared with retransmission)

  • Cooling output: 1 point (optional, shared with transmission)

  • Output types: 4-20 mA, 0-20 mA, or voltage pulse

PID and Control Functions

  • Proportional band: 0.1 to 999.9%

  • Integral time: 1 to 6000 sec. or OFF

  • Derivative time: 1 to 6000 sec. or OFF

  • ON/OFF control with adjustable hysteresis

  • High/low output limiters: -5.0 to 105.0%

  • Rate-of-change limiter: 0.1 to 100.0%/sec.

Analog Output Accuracy

  • ±0.1% of span for current output

  • Exceptions: ±5% of span for signals ≤1 mA

  • Accuracy measured at 23 ±2°C, 55 ±10% RH

Retransmission Output

  • 1 point standard (shared with 15V loop power)

  • 4-20 mA or 0-20 mA DC

  • Load resistance: 600 Ω or less

15V DC Loop Power Supply

  • Shared with retransmission output

  • Voltage: 14.5 to 18.0 V DC

  • Maximum current: about 21 mA (short-circuit protected)

Step Response Time

  • Within 1 second (10% to 90% input span change)

Relay and Transistor Outputs

The UT32A-000-11-00 includes multiple discrete outputs.

Relay Contact Output

  • Control relay: 1 C-form contact (3A at 250V AC or 30V DC)

  • Alarm outputs: 3 A-form contacts (1A at 240V AC or 30V DC)

  • Minimum load for control relay: 10 mA

  • Minimum load for alarm relay: 1 mA

Transistor Output

  • Open collector (sink current)

  • Capacity: up to 24V DC, 50 mA

  • Time resolution: minimum 200 ms

  • Use cases: alarm, FAIL output

Position Proportional and Heater Break Options

Position Proportional Output

  • Slide resistance input: 100 Ω to 2.5 kΩ

  • Current input: 4-20 mA DC with disconnection detection

  • Sampling period: 50 ms

  • Resolution: 0.1% of input span

  • Relay outputs: Two A-form contacts (3A at 240V AC or 30V DC)

Heater Break Alarm (/HA Option)

  • Measures heater current via external CT

  • Number of inputs: 2 points

  • CT input range: 0.0 to 0.1 Arms

  • Alarm setting: 0.1 to 300.0 Arms (or OFF)

  • Recommended CT: CTL-6-S-H or CTL-12L-30 from URD

  • Measurement period: 200 ms

  • Accuracy: ±5% of CT input range span ±1 digit

Power and Environmental Specifications

Power Supply

  • Rated voltage: 100 to 240V AC (+10%/-15%), 50/60 Hz

  • Option /DC: 24V AC/DC (+10%/-15%)

  • Power consumption: 15 VA (AC) / 7 VA (24V DC)

  • Allowable interruption: 20 ms at 100V AC

Isolation and Withstanding Voltage

  • Primary to secondary: 3000V AC for 1 minute (CE)

  • Primary terminals: power and relay outputs

  • Secondary terminals: analog I/O, contact input, communication

Environmental Conditions

  • Ambient temperature: -10 to 50°C (-10 to 40°C for side-by-side)

  • With CC-Link option: 0 to 50°C (0 to 40°C side-by-side)

  • Ambient humidity: 20 to 90% RH (no condensation)

  • Storage temperature: -25 to 70°C

  • Installation altitude: up to 2000 m above sea level

  • Warm-up time: 30 minutes minimum

Safety and EMC

  • Safety: IEC/EN 61010-1, UL 61010-1, CSA C22.2

  • EMC: EN 61326-1 Class A, EN 55011 Class A Group 1

  • IP rating: IP66 front panel (NEMA4 for hose-down)

Installation and Mounting

The UT32A-000-11-00 has a shallow 65mm depth. This makes it perfect for thin panels.

Mounting steps:
First, cut a 1/8 DIN panel opening (92 x 45 mm). Next, insert the controller from the front. Then, attach the mounting bracket from behind. Finally, tighten the screws evenly.

Do not mount units side-by-side without spacing if you need full IP66 protection. The IP66 rating does not apply to close side-by-side mounting.

Leave enough space for wiring and ventilation. Ambient temperature must stay below 40°C for side-by-side installations.

Packaging List

  • Yokogawa UT32A-000-11-00 controller – 1 unit

  • Mounting bracket – 1 piece

  • Panel gasket – 1 piece

  • Quick reference guide – 1 copy

  • Terminal cover – 1 piece

Note: No certificates or warranty documents are included in this package.

Shipping Information

We ship using global couriers.

  • FedEx

  • UPS

  • DHL

All shipments include tracking and anti-static protection.

Frequently Asked Questions (FAQ)

1. Can the UT32A-000-11-00 control both heating and cooling?
Yes, it can. This model supports heating/cooling control. You need to assign the cooling output to an available output point. The deadband is adjustable from -100.0 to 50.0%.

2. Does this controller have Ethernet communication?
No, the UT32A-000-11-00 does not include Ethernet. This base model supports CC-Link and RS485 only. For Ethernet, choose a different suffix code.

3. What is the ladder sequence function used for?
You can create simple logic sequences without a PLC. For example, interlock conditions, timer delays, or basic state machines. Use LL50A software (sold separately) to program it.

4. How do I change the PV display color?
The active color LCD changes automatically based on alarm conditions. You can configure the setpoints for white-to-red switching. This gives a clear visual alert to operators.

5. Is external power needed for a 2-wire transmitter?
No, not if you order the /LP option. That adds a 24V DC loop power supply. It provides 21.6 to 28.0V DC at up to 30 mA. Perfect for powering a 2-wire transmitter directly.



Attention: The above product information is sourced from the internet and cannot be guaranteed to be authentic. For specific product parameters and prices, please contact SpareTech PLC professionals in a timely manner.
Brand Name Yokogawa
Model No.UT32A-000-11-00
Product TypeDigital Indicating Controller
hasMerchantReturnPolicyAdjust according to reality
ShippingdetailsAdjust according to reality
The Yokogawa UT32A-000-11-00 is a 1/8 DIN digital indicating controller. It features a bright color LCD with PV color change. Universal input and PID control come standard. Its 65mm depth saves panel space. Ideal for temperature, pressure, and flow applications.
SpareTech PLC provides you with a PDF version of the instructions about Yokogawa UT32A-000-11-00, where you can download the Yokogawa UT32A-000-11-00 manual PDF for free:
Download PDF

Get a Professional Quote