Main image of Honeywell TC-PIB161 Digital Input Module 16-Point NAMUR

Honeywell TC-PIB161 Digital Input Module 16-Point NAMUR

TC-PIB161
Manufacturer: Honeywell
Series: Series C I/O
Model Number: TC-PIB161
Weight: 0.52kg
Condition: In Stock
Availability: 100% Original Brand New
Product Origin: U.S.A
Shipping port: Xiamen
Warranty: 12 Month

TC-PIB161 16-Point Digital Input Module by Honeywell

Product Introduction

The TC-PIB161 from Honeywell provides sixteen single-ended sinking input channels. All channels share a single common supply. This module complies with EN 50227 (NAMUR) standards.

You can use it with intrinsically safe proximity sensors and mechanical switches. The Honeywell TC-PIB161 carries a CENELEC II (1) 2G EEx ia/ib IIB/IIC T4 rating. Additionally, it offers configurable fault detection for four channel groups.

Technical Specifications

Input Characteristics

  • Input capacity: 16 single-ended sinking channels

  • Input type: NAMUR per EN 50227

  • Quiescent voltage: Approximately 8Vdc

  • Short-circuit current: Approximately 8mA

  • Switching point: 1.2 to 2.1mA

  • Switching hysteresis: Approximately 0.2mA

  • Minimum pulse length: >25 µs

  • Minimum pulse pause: >25 µs

  • Maximum switching frequency: 1kHz

Response and Update Times

  • Module input/output delay: 1ms for all channels

  • Backplane bus update: 1 to 64ms (depends on filter time setting)

  • Digital filter time: Configurable, applies to all channels together

Resolution and Accuracy

The TC-PIB161 delivers reliable switching detection. Its response time is 1ms across all sixteen channels. This makes it suitable for high-speed digital monitoring applications.

Permissible Field Circuit Values

For All Input Channels

  • Uo: 14.5V

  • Io: 15mA

  • Po: 40mW

  • Lo (IIB): 10mH maximum | Lo (IIC): 2mH maximum

  • Co (IIB): 1µF maximum | Co (IIC): 300nF maximum

  • Lo/Ro (IIB): 2.6 mH/ohm | Lo/Ro (IIC): 0.65 mH/ohm

Mechanical and Environmental Conditions

Operating Environment

  • Ambient temperature: –20°C to 70°C (–4°F to 158°F)

  • Storage temperature: –20°C to 100°C (–4°F to 212°F)

  • Max relative humidity: 95% non-condensing

  • Pollution gas test: Level G3 (ISA-S71.04-1985)

Shock and Vibration

  • Shock test: 15g peak, 11ms duration

  • Vibration test: 2g @ 10Hz to 500Hz (IEC 68-2-6)

  • Protection class: IP20 (requires IP54+ housing for field installation)

Physical Dimensions

  • Weight: 0.238 kg (0.52 lb)

  • Dimensions (H x W x D): 76 x 94 x 46 mm (3.0 x 3.7 x 1.8 inches)

  • Keyswitch position: 6

Standards and Certifications

The TC-PIB161 meets several international standards:

  • DIN EN 50014:1992

  • DIN EN 50020:1994

  • DIN EN 50284:1997

  • DIN IEC 721 (climatic conditions)

  • EMC: DIN EN 50081-2, DIN EN 50082-2, NAMUR NE 21

Certifications:

  • CENELEC: II (1) 2G EEx ia/ib IIB/IIC T4

  • DMT 98 ATEX E 037 X

Installation Guidelines

Follow these steps to install the Honeywell TC-PIB161 correctly.

First, confirm the keyswitch position is set to 6 on the terminal base. Then mount the module onto the base. Next, connect NAMUR sensors according to the terminal labeling.

For EMC compliance, use shielded multicore cable. Each channel does not require individual shields, but overall cable shielding is necessary. Additionally, field installations need an IP54 or better enclosure.

Finally, set the DIP switches to enable fault detection for the required channel groups. Configure the digital filter time based on your noise environment.

Packaging List

  • TC-PIB161 Digital Input Module (1 unit)

  • Anti-static protective bag

  • Quick installation guide (printed)

Note: Terminal bases, cables, and field sensors are sold separately.

Shipping Information

We ship worldwide using FedexUPS, or DHL. Tracking number is provided after dispatch.

Frequently Asked Questions (FAQ)

1. What type of sensors work with the TC-PIB161?
The TC-PIB161 accepts NAMUR proximity sensors and mechanical switches according to EN 50227. It supports both 2-wire and 3-wire NAMUR devices.

2. How do I enable fault detection for specific channels?
Use the four DIP switches on the bottom of the module. Each switch controls one group of four channels. Set the switch to ON to enable fault detection for that group.

3. What is the maximum switching frequency of this module?
The module supports up to 1kHz switching frequency. This assumes proper pulse width and pause time of at least 25 microseconds each.

4. Is there galvanic isolation between input channels?
No. All sixteen inputs share a common reference. However, isolation exists between inputs and the backplane bus. Isolation also exists between inputs and the power supply.

5. Can I use the TC-PIB161 without fault detection enabled?
Yes. Simply turn off all four DIP switches. The module will still read digital inputs normally. Lead break and short circuit alarms will not be reported.



Attention: The above product information is sourced from the internet and cannot be guaranteed to be authentic. For specific product parameters and prices, please contact SpareTech PLC professionals in a timely manner.
Brand NameHoneywell
Model No.TC-PIB161
Product TypeDigital Input Module
hasMerchantReturnPolicyAdjust according to reality
ShippingdetailsAdjust according to reality
The Honeywell TC-PIB161 is a 16-channel digital input module for NAMUR proximity sensors and switches. It features intrinsic safety, configurable fault detection per channel group, and a fast 1ms response time. Ideal for hazardous area digital signal monitoring.
SpareTech PLC provides you with a PDF version of the instructions about Honeywell TC-PIB161, where you can download the Honeywell TC-PIB161 manual PDF for free:
Download PDF