Woodward 8440-1809 easYgen-1000 Series Controller for Non-Paralleling Gensets

Reliable Control for Mobile and Standby Power

The Woodward 8440-1809 comes from the easYgen-1000 series, specifically the easYgen-1500 model. It serves specialized non-paralleling applications. These include mobile power units and emergency standby systems. You can configure this controller for 1 or 2 breaker operation. Additionally, it supports flexible start-stop logic for both diesel and gas engines.

Key parameters include an input resistance of approximately 6.7 kΩ and a linear measuring range of 1.5 x V. Load rating (GP) is 2.00 Aac @ 250 Vac. Maximum power consumption stays below 0.15 W. Storage temperature ranges from -22 to 176 °F.

Alarm Classes and Testing Features

The 8440-1809 uses six alarm classes: A, B, C, D, E, and F. Class A remains class A, and class B stays class B. However, classes C, D, E, and F all convert to class B alarms. This simplifies alarm management.

You can set up your controller with or without load. For a load test, start the unit in automatic mode. A special message will not appear on the display screen. If the mains fails during starting, the unit keeps running. It will only stop after the mains returns and the settling time expires.

Control Interface and Display

This controller features a built-in LCD display for local monitoring. It operates on 12-24 V DC power. The unit mounts directly onto a panel. Supported communication protocols include CAN Open, J1939, and Modbus RTU. Modem connection is also available.

Moreover, the Woodward 8440-1809 provides true RMS voltage and current sensing. It monitors both generator and mains. Complete engine and generator protection is standard. Metering functions give you real-time operational data.

Advanced Logic and Connectivity

The LogicsManager™ tool combines measured values, internal conditions, and I/O states. It uses boolean operators and programmable timers. Therefore, you can create complex control sequences with ease.

Advanced CAN communication connects to most common engine ECUs. You can also link to the Woodward IKD 1 module for I/O expansion. For NFPA-compliant installations, connect the Easylite-100 remote annunciation panel. Furthermore, remote-start capability allows unattended operation.

Installation and Environmental Notes

Install the 8440-1809 in a dry, vibration-free panel. Ambient temperature should stay between -30°C and +80°C (-22°F to 176°F) for storage. Operating range is typically -20°C to +70°C. Use shielded cables for analog inputs to avoid noise interference.

Packaging List

  • Woodward 8440-1809 controller unit (1 pc)

  • Panel mounting clips and screws (4 sets)

  • Terminal block connectors (pre-installed)

  • Quick reference guide (paper copy)

  • Configuration software CD

Note: No certificate or warranty document is included in the package.

Shipping Information

We ship all orders via FedEx, UPS, or DHL. Delivery takes 3–7 business days worldwide. Tracking number will be provided within 24 hours after dispatch.

Frequently Asked Questions (FAQ)

1. Can the Woodward 8440-1809 parallel multiple gen-sets?
No, the 8440-1809 is designed for non-paralleling applications. For paralleling up to 32 units, consider the easYgen-3000 series like the 8440-2054.

2. What languages does the LCD display support?
The display supports 10 selectable languages. These include English, Spanish, French, German, Italian, Portuguese, Chinese, Russian, Turkish, and Polish.

3. Does this controller work with J1939 diesel engines?
Yes, the 8440-1809 supports J1939 communication. It also supports CAN Open and Modbus RTU. This allows easy connection to most common engine ECUs.

4. What happens if mains fails during a load test?
If the mains fails while starting the unit in automatic mode, the controller keeps running. It will not shut down until the mains returns and the settling time expires.

5. Can I expand the I/O on the Woodward 8440-1809?
Yes, you can connect the Woodward IKD 1 module via CAN communication. This expands the onboard I/O set for additional inputs and outputs.



Attention: The above product information is sourced from the internet and cannot be guaranteed to be authentic. For specific product parameters and prices, please contact SpareTech PLC professionals in a timely manner.
Brand NameWoodward
Model No.8440-1809
Product TypeGenset Control Unit
hasMerchantReturnPolicyAdjust according to reality
ShippingdetailsAdjust according to reality
The Woodward 8440-1809 belongs to the easYgen-1000 series. It is designed for non-paralleling mobile power and emergency standby applications. This unit offers flexible breaker configuration, remote-start capability, and complete engine protection. A built-in LCD display supports 10 languages. Advanced CAN communication allows connection to engine ECUs and I/O expansion modules.
SpareTech PLC provides you with a PDF version of the instructions about Woodward 8440-1809, where you can download the Woodward 8440-1809 manual PDF for free:
Download PDF

Get a Professional Quote